Product Description
Applications :
♦Hybrid and off grid solar power system
♦ UPS Systems
♦Wind solar energy system
♦ Signal system , emergency lighting system , security system
♦Telecommunication Equipment
♦Power station and plant room
Specification
Specifications of OPzV Batteries 2V 800AH
Nominal Voltage | 2V | ||||
Nominal Capacity | 800AH@10hours rate F.V.(1.80V/Cell) | ||||
Approx. Weight | 62KG(136.68lbs) | ||||
Termainals | M8 Female Large Size Copper Post | ||||
Internal Resistance | <=0.33mΩ (Fully Charged) | ||||
Max. Discharge Current | 8000A (3 See) | ||||
Max. Charge Current | 200A | ||||
Operating Temperature Range | Charge: -20℃~+50℃ (-4℉~+122℉) Discharge: -40℃~+55℃ (-40℉~+131℉) Storage: -20℃~+40℃ (-4℉~+104℉) | ||||
Self Discharge | About 2.0% of Capacity Delined per Month at 25℃ |
Constant Power Discharge Characteristics at 25℃/77℉ Unit: W | ||||||||||||||||
F.V/Time | 15MIN | 30MIN | 1HR | 2HR | 3HR | 5HR | 10HR | 20HR | ||||||||
1.70V | 1462 | 1190 | 922 | 542 | 427 | 293 | 158 | 89.7 | ||||||||
1.75V | 1346 | 1142 | 884 | 528 | 417 | 289 | 156 | 88.3 | ||||||||
1.80V | 1192 | 1074 | 779 | 514 | 402 | 284 | 154 | 88.2 | ||||||||
1.90V | 886 | 799 | 635 | 472 | 353 | 256 | 138 | 81.6 |
Charge Voltage
Cycle Use: 2.35~2.40V(+/-4mV)
Max Current: 200A
Constant Current Discharge Characteristics at 25℃/77℉UNit: A | ||||||||||||||||
F.V/Time | 15MIN | 30MIN | 1HR | 2HR | 3HR | 5HR | 10HR | 20HR | ||||||||
1.70V | 846 | 688 | 468 | 286 | 212 | 142 | 82.0 | 46.4 | ||||||||
1.75V | 752 | 624 | 448 | 278 | 208 | 141 | 81.0 | 46.1 | ||||||||
1.80V | 626 | 560 | 416 | 266 | 200 | 139 | 80.0 | 45.9 | ||||||||
1.90V | 416 | 392 | 312 | 220 | 172 | 124 | 71.5 | 42.1 |
Float USE
2.25~2.30V(+/-3mV)
Curves
Curves of 2V 800AH OPzV Tulubar GEL Battery
Factory & Production
Packing & Delivery
Projects of Battery
Recommend Products