Model
| JLSP-DC85/40 | JLSP-DC225/40 | JLSP-DC350/40 |
IEC Classification
| Class II | Class II | Class II |
DC Network Un (50/60Hz)(V)
| 24,48 | 110 | 220 |
Max. continuous operationg voltage Uc (V)
| 85 | 225 | 350 |
Nornimal discharge current In (kA)
| 20 | 20 | 20 |
Max. discharge current(8/20us) Imax (kA)
| 40 | 40 | 40 |
Voltage protection level Up (kV)
| ≤0.8 | ≤1.2 | ≤1.4kV |
Max. backup fuse (A)
| 35A DC (gG) | 35A DC (gG) | 35A DC (gG) |
Response time tA
| ≤25ns | ≤25ns | ≤25ns |
Capacity of withstand short circuit
| 300A | 300A | 300A |
Operating temperature
| -40°C∼+85°C | -40°C∼+85°C | -40°C∼+85°C |
Relative humidity
| ≤95%(25°C) | ≤95%(25°C) | ≤95%(25°C) |
Max. cross-sectional area of wire
| 25mm2 multi-strand cord | 25mm2 multi-strand cord | 25mm2 multi-strand cord |
Dimensions (1P) (W*L*H) (mm)
| 18X90X62 | 18X90X62 | 18X90X62 |
Mounting
| DIN Rail 35mm | DIN Rail 35mm | DIN Rail 35mm |
Protection rating
| IP 20 | IP 20 | IP 20 |
Housing material
| PBT | PBT | PBT |
Flame retardant rating
| UL 94 V-0 | UL 94 V-0 | UL 94 V-0 |
Capacity of remote signaling contact
| 250VAC/0.5A 30VDC/3A | 250VAC/0.5A 30VDC/3A | 250VAC/0.5A 30VDC/3A |
Max.cross-sectional area of wire for remote signaling contact
| 1.5mm² multi-strand cord/single cord | 1.5mm² multi-strand cord/single cord | 1.5mm² multi-strand cord/single cord |
Status indicator
| Normal: Green Malfunction: Red | Normal: Green Malfunction: Red | Normal: Green Malfunction: Red |
Standards compliance
| EN50539-11 IEC61643-31 GB/T 18802.31 | EN50539-11 IEC61643-31 GB/T 18802.31 | EN50539-11 IEC61643-31 GB/T 18802.31 |