Model | JLSP-GA275/40 | JLSP-GA275/80 | JLSP-GA275/100 |
IEC Class | Class Ⅱ | Class Ⅱ | Class Ⅱ |
AC Network UN(50/60Hz)(V) | 202,230,102/208 (TN/TT/IT) | 202,230V,102/208 (TN/TT/IT) | 202,230,102/208 (TN/TT/IT) |
Max.continuous operating voltage Uc(V) | 275 | 275 | 275 |
Nominal discharge current In(kA) | 20 | 40 | 60 |
Max. Discharge current(8/20us) Imax(kA) | 40 | 80 | 100 |
Voltage Protection level Up(kV) | ≤1.4 | ≤1.5 | ≤1.8 |
Max. backup fuse(A) | 100(gG) | 100(gG) | 125(gG) |
Response time tA | ≤25ns | ≤25ns | ≤25ns |
Capacity of withstand short circuit | 25kA | 25kA | 25kA |
Operating temperature | -40℃~+85℃ | -40℃~+85℃ | -40℃~+85℃ |
Relative humidity | ≤95%(25℃) | ≤95%(25℃) | ≤95%(25℃) |
Max.cross-sectional area | 25mm2 multi-strand cord | 35mm2 multi-strand cord | 35mm2 multi-strand cord |
Dimensions (1P) (W×L×H)(mm) | 18×90×62 | 27×90×62 | 36×90×65 |
Mounting | DIN Rail 35mm | DIN Rail 35mm | DIN Rail 35mm |
Protection rating | IP 20 | IP 20 | IP 20 |
Housing material | PBT | PA66 | PA66 |
Flame retardant rating | UL94 V-0 | UL94 V-0 | UL94 V-0 |
Capacity of remote signaling contact | 250VAC/0.5A 30VDC/3A | 250VAC/0.5A 30VDC/3A | 250VAC/0.5A 30VDC/3A |
Max.cross-sectional area for remote signaling contact | 1.5mm2 multi-strand cord / single cord | 1.5mm2 multi-strand cord / single cord | 1.5mm2 multi-strand cord / single cord |
Status indicator | Normal:green / malfunction:red | Normal :transparent / malfunction:red | Normal :transparent / malfunction:red |
Standards compliance | EN61643-11,IEC61643-11,GB/T 18802.11 | EN61643-11,IEC61643-11,GB/T 18802.11 | EN61643-11,IEC61643-11,GB/T 18802.11 |