Homepage|Business Center|Save the Page|Get the App
普通会员

Shenzhen Pusinuo Optoelectronic Technology Co., Ltd.

Product Category
  • No Category Yet
Search
 
Link
  • No links
Home > Products > Led emergency driver DC80-155V recharge time 24hours in good quality
Led emergency driver DC80-155V recharge time 24hours in good quality
Click on the image to view the original image
Product: views:9Led emergency driver DC80-155V recharge time 24hours in good quality 
Unit Price: Negotiated
Min.Order:
Supply:
Delivery: Shipment within days since the date of payment
Valid until: Long Term
Updated on: 2020-12-23 09:59
  Negotiated
Product Details

LED EMERGENCY DRIVER               AC-LEDEM Series
PRODUCT SPECIFICATION SHEET                                       EMA Series High output voltage Self-test Series
DESCRIPTION:
EMA series emergency drive is UL listed led emergency driver for Field and factory installation that allows
the same led fixture to be used for both normal and emergency operation.In the event of a power failuere.
The emergency driver switches to emergency mode and operates the existing fixture to 90 minutes.
The unit contains a battery.charge,and converter for individual fixture requirements.This module will
opeate an LED array load at 15w,25w,40w with constant power at a rated output voltage of 170VDC. The
patented constant power design of the module maintians the output wattage to LED array even as the
system voltage diminished resaulting in a constant illumination level for entire emergency runtime.
The integrated self-diagnostic circuitry will automatically conduct 1 monthly 30- seconds and annual
90-minute tests to verify proper emergency capability per Life Safety Code requirements.
ADVANTAGES:
1.Optimized for higher voltage LED luminaires with 170VDC driver output.
2.High Effciency Performance meets CEC effciency standards (CEC-400-2014-009-CMF).
3.Increased illumination output designed for elevated fxtures
4.UL Listed for factory and feld installation
5.Self-sensing output voltage operates various
6.product types reducing product SKUs for emergency options.
SPECIFICATION:
Input Voltage
(Universal) 120-277VAC, 50/60Hz
Input Power (120V/347V)
7 Watts (max)
Output Voltage
DC25-230VDC
Output Power
8,15,20,30 Watts
Power Factor
0.85
EMI (Radiated and Conducted)
FCC Class A (charge and EM modes)
Surge Protection
Meets ANSI/IEEE C62.41.2-2002
Emergency Operation
90 minutes
Charge Time
24 Hour Recharge
Battery
Lithium battery 0° to 55° C
Weight
1.21kg
Approval
cUL Listed for factory and field installation
FEATURES:
1.UL 924 Listed for U.S. and Canada
2.Five mounting confgurations available
3.Long-life, maintenance-free, high temperature recyclable Lithium battery
4.5-Year Warranty.
5.Rated for use in plenum, damp location, and enclosed and gasketed fixtures
6.RoHS Compliant
DIMENSION:
Case- 12.36'' X2.28''X1.5 ''(314mmX58mm X38mm)
Mounting Center-11.8''(300mm)
Flexible Conduit 13''(330mm)
WIRING DIAGRAM:
1.The wattage<120w wiring diagram
2.The wattage >120w wiring diagram
Self-Diagnostic:
The integrated self-diagnostic circuitry will automatically conduct monthly 30-second and
annual 90-minute tests to verify proper emergency capability per Life Safety Code
requirements.
Press the test button to cut the power to the AC driver and switch the system to emergency
mode. Release the test button to return to normal mode. Switch off the circuit breaker to
simulate a full power outage.
NFPA 101, Life Safety Code outlines the following schedule:
Monthly - Insure that the test button light is illuminated. Conduct a 30 second discharge test by
depressing the test button.
The LED load should operate at reduced output.
Annually - Insure that the test button is illuminated. Conduct a full 90 minute discharge test.
The unit should operate as intended for the duration of the test.
“Written records of the testing shall be kept by the owner for inspection by the authority
having jurisdiction.”
询价单
total0items  Comments