Product Description
EMB series emergency drive is UL listed led emergency driver for Field and factory installation that allows
the same led fixture to be used for both normal and emergency operation.In the event of a power failuere.
The emergency driver switches to emergency mode and operates the existing fixture to 90 minutes.
The unit contains a battery.charge,and converter for individual fixture requirements.This module will
opeate an LED array load at 8w,15w,20w,30w with constant power at a rated output voltage of 25-230V.
The patented constant power design of the module maintians the output wattage to LED array even as the
system voltage diminished resaulting in a constant illumination level for entire emergency runtime.
The integrated self-diagnostic circuitry will automatically conduct 3 monthly 30- minutes and annual
90-minute tests to verify proper emergency capability per Life Safety Code requirements.
Ordering Information:
Place of Origin |
China |
Bulb Type |
LED |
Battery Type |
Lithium battery 0° to 55° C |
Material |
Galvanized steel case |
Usage |
LED lighting |
Certification |
UL Listed, CEC Title 20, BC, FCC, RoHs, UL, cUL, Class 2, Class P, BC, CEC Title 20 |
Specifications |
8W |
Warranty(Year) |
5-Year |
Product Series |
LED Emergency Driver |
Warranty |
5 Years |
Type |
Constant power |
Emergency Backup Mode |
At least 90 Minutes |
Feature |
Compatible with any AC Driver |
1.Optimized for higher voltage LED luminaires with 25-230VDC driver output.
2.High Effciency Performance meets CEC effciency standards (CEC-400-2014-009-CMF).
3.Increased illumination output designed for elevated fxtures
4.UL Listed for factory and feld installation
5.Self-sensing output voltage operates various
6.product types reducing product SKUs for emergency options.
SPECIFICATION:
Input Voltage ......................................................... (Universal) 120-277VAC, 50/60Hz
Input Power (120V/277V).................................................................. 7 Watts (max)
Output Voltage .............................................................................DC25-230VDC
Output Current ..................................................0.125A (@25VDC) - 0.1A (@230VDC)
Output Power..................................................8,15,20,30 Watts
Power Factor ................................................................................................... ≥ 0.85
EMI (Radiated and Conducted) ......................FCC Class A (charge and EM modes)
Surge Protection ....................................................Meets ANSI/IEEE C62.41.2-2002
Emergency Operation ............................................................................... 90 minutes
Charge Time .............................................................................24 Hour Recharge
Battery..........................................................................Lithium battery 0° to 55° C
Weight................................................................................0.41kg
Approval ...................................................cUL Listed for factory and field installation
Safety Regulation:
Certificate | Approval Marks | Standard | Valid | Remarks |
UL | UL924 | YES | North America | |
cUL | CAN/CSA-C22.2 NO. 141 | YES | Canada | |
BC | CEC Title 20 | YES | California | |
FCC | FCC | YES | North America |
DIMENSION:
Case-7.3''x1.5''x0.98''(186mmx38mmx25)
Mounting center-7.0''(179mm)
Case Length | 186mm |
Case Width | 38mm |
Case Height | 25mm |
Mounting Length | 179mm |
WIRING DIAGRAM:
SELF-Diagnostic:
The integrated self-diagnostic circuitry will automatically conduct monthly 30-second and
annual 90-minute tests to verify proper emergency capability per Life Safety Code requirements.
Press the test button to cut the power to the AC driver and switch the system to emergency mode.
Release the test button to return to normal mode. Switch off the circuit breaker to simulate a full
power outage.
NFPA 101, Life Safety Code outlines the following schedule:
Monthly - Insure that the test button light is illuminated. Conduct a 30 second discharge test by
depressing the test button. The LED load should operate at reduced output.
Annually - Insure that the test button is illuminated. Conduct a full 90 minute discharge test.
The unit should operate as intended for the duration of the test.
“Written records of the testing shall be kept by the owner for inspection by the authority having jurisdiction.”
Company Profile
Packing & Shipping