DESCRIPTION
EMB series emergency drive is UL listed led emergency driver for Field and factory installation
that allows the same led fixture to be used for both normal and emergency operation.In the
event of a power failuere.the emergency driver switches to emergency mode and operates
the existing fixture to 90 minutes. The unit contains a battery.charge,and converter for
individual fixture requirements.This module will opeate an LED array load at 8w,15w,20w,30w
with constant power at a rated output voltage of 25-230V. The patented constant power design
of the module maintians the output wattage to LED array even as the system voltage
diminished resaulting in a constant illumination level for entire emergency runtime.
The integrated self-diagnostic circuitry will automatically conduct 3 monthly 30- minutes and
annual 90-minute tests to verify proper emergency capability perLife Safety Code requirements.
ADVANTAGES
1.Optimized for higher voltage LED luminaires with 25-230VDC driver output.
2.High Effciency Performance meets CEC
3.effciency standards (CEC-400-2014-009-CMF).
4.Increased illumination output designed for elevated fxtures
5.UL Listed for factory and feld installation
6.Self-sensing output voltage operates various
7.product types reducing product SKUs for emergency options.
Features
1.UL 924 Listed for U.S. and Canada
2.Five mounting confgurations available
3.Long-life, maintenance-free, high temperature recyclable Lithium battery
4.5-Year Warranty.
5.Rated for use in plenum, damp location, and enclosed and gasketed fixtures
6.RoHS Compliant
Specification
Input Voltage
|
(Universal) 120-277VAC, 50/60Hz
|
Input Power (120V/277V)
|
7 Watts (max)
|
Output Voltage
|
DC25-230VDC
|
Output Current
|
0.125A (@25VDC) - 0.1A (@230VDC)
|
Output Power
|
8,15,20,30 Watts
|
Power Factor
|
>0.85
|
EMI (Radiated and Conducted)
|
FCC Class A (charge and EM modes)
|
Surge Protection
|
Meets ANSI/IEEE C62.41.2-2002
|
Emergency Operation
|
90 minutes
|
Charge Time
|
24 Hour Recharge
|
Battery
|
Lithium battery 0° to 55° C
Ni-MH battery 5° to 65° C
|
Weight
|
0.41kg
|
Approval
|
cUL Listed for factory and field installation
|
DIMENSION
Case-7.3''x1.5''x0.98''(186mmx38mmx25)
Mounting center-7.0''(179mm)
case length | 186mm |
case width | 38mm |
case height | 25mm |
mounting length | 179mm |
WIRING DIAGRAM
The wattage<120w wiring diagram
The wattage >120w wiring diagram
Self-Diagnostic
The integrated self-diagnostic circuitry will automatically conduct monthly 30-second and
annual 90-minute tests to verify proper emergency capability per Life Safety Code
requirements.
Press the test button to cut the power to the AC driver and switch the system to emergency
mode. Release the test button to return to normal mode. Switch off the circuit breaker to
simulate a full power outage.
NFPA 101, Life Safety Code outlines the following schedule:
Monthly - Insure that the test button light is illuminated. Conduct a 30 second discharge test
by depressing the test button. The LED load should operate at reduced output.
Annually - Insure that the test button is illuminated. Conduct a full 90 minute discharge test.
The unit should operate as intended for the duration of the test.
“Written records of the testing shall be kept by the owner for inspection by the authority
having jurisdiction.”