EMA series emergency drive is UL listed led emergency driver for Field and factory installation that allows
Model | Voltage input | Output power | Output voltage | Emergency time |
EMA25ACT-170
|
100-347V | 25W | 170vdc(120Vac) | 90 mins |
Parameter
|
Min.
|
Typical
|
Max.
|
Remarks
|
Rated Input Voltage (Vac)
|
100
|
--
|
347 | |
Input Voltage Range (Vac)
|
90 |
--
|
380 | |
Input Frequency Range (Hz)
|
47 | 50/60 | 63 | |
Max. Input Current(A)
|
-- | -- | 0.2 | 120Vac, charging |
Max. Input Power(W) | -- | -- | 12 | 120Vac, charging |
Input Surge Current(A) | -- | -- | 10 | 347Vac/60Hz, cold start |
Standby Power (W) | -- | -- | 0.8 | 347Vac/60Hz, charged |
Power Factor | 0.85 | -- | -- | Vin=120Vac/60Hz (charging) |
THDI | -- | 15% | 20% | Vin=120-277Vac/60Hz
(charging)
|
Max. Load(W) | -- | -- | 250 | Max. input power of LED
fixture. And dimming to Min.
input power(before dimming
to off) of LED fixture must be
less than 25W.
|
Parameter
|
Min.
|
Typical
|
Max.
|
Remarks
|
No Load Output Voltage (Vdc)
|
-- |
--
|
250 | |
Emergency Output Power (W)
|
-- |
--
|
18 |
Max. output power limited to 30W
|
Instantaneous Output Power (W)
|
-- | -- |
--
|
Emergency, cold start peak output, last time 10 seconds
|
Power-up Time (S)
|
--
|
--
|
3
|
120Vac, charging
|
Response Time (S)
|
--
|
--
|
3 |
Switch from mains supply cuts to Emergency output
|
Emergency Duration Time
|
90
|
--
|
--
|
|
Output Voltage (Vdc)
|
25 | -- | 230 | approximate value, varies with the battery voltage |
Certificate
|
Approval
Marks
|
Standard
|
Valid
|
Remarks
|
UL |
UL924
|
YES
|
North America
|
|
cUL |
CAN/CSA-C22.2 NO. 141
|
YES
|
Canada
|
|
BC |
CEC Title 20
|
YES
|
California
|
|
FCC |
FCC
|
YES
|
North America
|
Case length | 314mm |
Case Height | 38mm |
Case Width | 58mm |
Mounting lenght | 330mm |
WIRING DIAGRAM:
SELF-Diagnostic:
The integrated self-diagnostic circuitry will automatically conduct monthly 30-second and annual
90-minute tests to verify proper emergency capability per Life Safety Code requirements.
Monthly - Insure that the test button light is illuminated. Conduct a 30 second discharge test by
depressing the test button.The LED load should operate at reduced output.
Annually - Insure that the test button is illuminated. Conduct a full 90 minute discharge test.
The unit should operate as into endedfor the duration of the test.“Written records of the testing
shall be kept by the owner for inspection by the authority having jurisdiction.”