Homepage|Business Center|Save the Page|Get the App
普通会员

Yueqing Taixin Electric Co., Ltd.

Product Category
  • No Category Yet
Search
 
Link
  • No links
Home > Products > GKR-02 Voltage Monitoring Device Relay Phase Failure And Phase-sequence Protection Relay Din Rail Motor Protection
GKR-02 Voltage Monitoring Device Relay Phase Failure And Phase-sequence Protection Relay Din Rail Motor Protection
Click on the image to view the original image
Product: views:4GKR-02 Voltage Monitoring Device Relay Phase Failure And Phase-sequence Protection Relay Din Rail Motor Protection 
Branch: taxnele
Size: 5X5X5 cm
Unit Price: Negotiated
Min.Order:
Supply:
Delivery: Shipment within days since the date of payment
Valid until: Long Term
Updated on: 2019-11-19 19:17
  Negotiated
Product Details
Overview
Quick Details
Place of Origin:
Zhejiang, China
Brand Name:
taxnele
Model Number:
12v 500A relay
Theory:
Electromagnetic Relay
Usage:
Auto
Size:
Miniature
Protect Feature:
Sealed
Contact Load:
Low Power
Product name:
GKR-02 Motor Protection
Color:
black
Function:
GKR-02 Motor Protection
Coil voltage:
12V 24V
Condition:
100%new

Packaging & Delivery

Selling Units:
Single item
Single package size: 
5X5X5 cm
Single gross weight:
1.0 kg
Package Type:
paper packing
Lead Time:
Quantity(Piece)1 - 50>50
Est. Time(days)7To be negotiated

1.Product attributes

GKR ve DGR series "over and under voltage" moitoring devices are adjustable "delay OFF"protection devices. they are mainly used for protection for 3-phase and single-phase systems-such as electronic command and control systems,capacitors fo power compensation, switch-boards ,air-condition systems,motors etc.

Utilization and Operation Principles

For all relays

"on" is the supply led

"out" is normal led

"U>"is over voltage error led

"U<"is under voltage errror led

1-When the device is energized for the first time."On" led is ON and if the monitored voltageare within the adjusted range "Out" led is ON and output relay switches ON.

2-When any of the phase/phases fall(s) below the adjusted interval,"U<" error led turns ON,after 0.1-10sec output relay switched OFF and "OUT" led turns OF.

3-When any of the phase/phases exceed(s) the adjusted interval,"U>" error led turns ON,after0.1-10 sec output relay switches OFF and "Out"led turns OFF.

look at table 1

*For under voltage monitoring device switched OFF its output relay instantaneously when the measured voltage(s) fall(s) below 50% of its nominal value.

For over voltage monitoring device switches OFF its output relay immediately when the measured voltage(s) exceeds 50% fo its nominal value.

GKR-02F /GKRC-02F/ GKRC-02FA /GKR-03F/GKRC-03F/ switches off output relay instantaneously in case of incorrect phase sequence then all leds turn off except "ON" led.

Technical Data:

Rated voltage(Un)Look it the label of the device
Rated frquuency50/60Hz
Operating range(0.9-1.1)×Un
Voltage adjustmentMax: (1,05-1,03) ×Un
Min: (0,70-0,95) ×Un
Delay time0.1-10sn.min.(adjustible)
Output contact1C/O 8A,2000VA,
Set point hysteresis3%
Ambient temperature-5°C;+50°C
installitionSurface mounted or rail mounted
DimensionType PK10/PK21/PK25
Protection classIP20

 

      2.Product display

 

询价单