Homepage|Business Center|Save the Page|Get the App
普通会员

Wofu Fire & Security Equipment Co., Ltd. (Yongzhou City)

Product Category
  • No Category Yet
Search
 
Link
  • No links
Home > Products > 70Ltr HFC-227ea gas fire suppression system Cylinder
70Ltr HFC-227ea gas fire suppression system Cylinder
Click on the image to view the original image
Product: views:270Ltr HFC-227ea gas fire suppression system Cylinder 
Branch: welfare
Unit Price: Negotiated
Min.Order:
Supply:
Delivery: Shipment within days since the date of payment
Valid until: Long Term
Updated on: 2019-10-16 21:09
  Negotiated
Product Details
Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
welfare
cylinder material:
maganest Steel
cylinder valve:
brass material
color:
Red Epoxy polyster or red polyster coating
cylinder capacity:
70L
cylinder size:
D300*1120*6mm
Supply Ability
Supply Ability:
100 Set/Sets per Month
Packaging & Delivery
Packaging Details
Wooden Case
Port
guanghzou

70L HFC-227ea gas cylinder

 

1.HFC-227EA fire extinguishing system introduction:

 

HFC-227ea is a clean extinguishing agent, which would completely vaporized in the air, and well insulated. Its total flooding mode is applicable to electric fire, liquid fire or fusible solid fire, solid surface fire, gas fire which gas supply is cut before extinguishing. And it is able to protect computer room, communication room, substation room, hi-tech device room, generator room, gasoline storeroom, combustible chemical storeroom, libraries, data room, archives, treasuries, etc. We are manufacture HFC-227ea system that is well structured, reliable, and widely applied to computer rooms, archives, program control exchange engine rooms , TV broadcast center, financial organizations and government departments.

 

2.HFC-227EA Gas cylinder main technical parameters:

2.1 Storage of cylinder: 40L/70L/100L/120L/150L/180L
2.2 Storage Pressure: 2.5MPa/4.2MPa(20)
2.3 Maximum Working Pressure (50): 3.4MPa/5.3MPa
2.4 Operating Method: electromagnetic starter; emergency mechanical starter
2.5 Nitrogen pressure of the electromagnetic driving device: 6.0±1.0MPa (20)
2.6 Starter power of the electromagnetic driving device: DC24V/1.5A
2.7 Extinguishing agent filling density: ≤1150kg/m3
2.8 Extinguishing agent spurting time: ≤8s

2.9 Protective Area Temperature: 0~50
2.9 Cylinder spurting allowance: ≤2kg/bottle
2.10 Cylinder-room temperature requirement: -10~50

 

 

3.HFC-227ea gas cylinder packing pictures:

 

Check and test the cylinder before packing,use bubble bag wrap cylinder,then packing into non fumigation wooden case,good protect it,avoid break and crash.

 

Company Information

 

询价单
total0items  Comments