Asenware Conventional 8 Zone Fire Alarm Panel 2166 Series

  • Unit Price: Negotiable
  • Brand:

  • Origin:

    China

  • Categories:Lights & Lighting
  • Validity Period:

    Long Term

  • Published on:

    2019-10-16 23:20

Other Products
CB Listed Twin LED Spot Emergency Lighting
¥Negotiable 12Views

CB Listed Twin LED Spot Emer

Recommend  
Asenware Factory Cost Conventional Emergency Light System Twin Lamp LED Emergency Light AW-EL207 for Shopping Center
¥Negotiable 9Views

Asenware Factory Cost Conven

Recommend  
Ceiling Mounted Dual LED Emergency Lighting System
¥Negotiable 15Views

Ceiling Mounted Dual LED Eme

Recommend  
Long Lasting Automatic  LED Twin Lamp Emergency Light Fire Indicator System
¥Negotiable 10Views

Long Lasting Automatic LED

Recommend  
Non Maintained Running Man Emergency Escape Lighted Light rechargeable Acrylic Pane Led Exit Sign
¥Negotiable 8Views

Non Maintained Running Man E

Recommend  
You may like
  • Product Description
  • Company Overview

Product Information

Brand:

none

Address:

China

Min.Order:

none

Supply:

none

Valid until:

Long Term

Product Details

Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
GUTAFIRE
Model Number:
GT-P1008
Product name:
Asenware Conventional 8 Zone Fire Alarm Panel 2166 Series
Capacity:
1-32zones
Zone:
8Zones
Wiring method:
2Wires
Usage:
Fire Protection
Model:
Conventional
Certificates:
CE IS09001
Supply Ability
Supply Ability:
200000 Piece/Pieces per Week
Packaging & Delivery
Packaging Details
Standard safety export package / carton (Box + Foam) or as customized
Port
Zhongshan
Product Description

8 Zone Fire Alarm Panel ,8 Zone Fire Alarm Panel ,8 Zone Fire Alarm Panel

Guta Conventional 8 Zone Fire Alarm Panel 2166 Series

ITEM

1Zone panel

2Zone panel

4-8Zone panel

4-32 Zone panel

Model No.

AW-CFP2166-01

AW-CFP2166-02

AW-CFP2166-04-8

AW-CFP2166-04-32

Power specification

 

Mains supply voltage

110VAC or 240VAC

Internal power supply

27.2VDC

Total output current limited

500mA @240VAC

500mA @240VAC

3A @ 240VAC

3A @ 240VAC

Main supply monitor for fault

Yes

Battery protection for low voltage

Yes

Batteries (default configuration)

12V2AH*2

Detector circuit specification

 

Number of circuit

1

2

4-8

4-32

Line fault monitor for open circuit

Yes

Line fault monitor for short circuit

Yes

Line fault monitor for detector removal

Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor

End of Line device

6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Detector continuity diodes

Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)

Call point resistor value

470 to 680 Ω, 0.225 or 0.5 watt

Maximum number of smoke/heat detectors per zone

20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.

Maximum number of manual call points per zone

No limit

Sounder circuit specification

 

Number of general circuits

2

End of line resistor value

6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Line fault monitor for open circuit

Yes

Line fault monitor for short circuit

Yes

Outputs fused AT

400mA

Maximum number of bells @ 20mA of each sounder output

20

Fuses

 

27VDC fuse

3A F 20mm

Fire and fault output

 

Output type

Dry relay output :NC and NO relay; wet source output

Maximum current

100mA

Connection block

 

Largest acceptable conductor size

2.5mm2

Smallest acceptable conductor size

0.75mm2

Size and weight

 

 

Dimensions(mm)

272*200*70mm

320*231*90mm

395X502X124

362X565X124

Weight (without batteries)

4kg

5kg

7kg

8kg

Weight (with batteries)

5.8kg

6.8kg

9.6kg

12.5kg

 

 

Packaging & Shipping

Packaging Details: Standard safety export package / carton (Box + Foam) or as customized

Delivery Detail: one week

 

Our Services

1.    OEM/ODM services.

2.    Professional technical team.

3.    Offer Free technical support whenever you need.

4.    One year warranty and technical maintenance

 

 Guta Conventional 8 Zone Fire Alarm Panel 2166 Series

Company Information

Guta, professional manufacturer of fire alarm and fire suppression system since 2005.Our headquarter is in London,UK, with factory Shenzhen,China.

Our company"s products have passed CE certification, SASO certification, other international certification is also in the process. We keep our best
service for our customers, and have 12 years of export experience with a technologically advanced team of engineers to design and install for overseas project.

 

Product range:

Addressable fire alarm system(2100 series for Big project,2189 series for small project)
Conventional fire alarm system(2166 series)
FM200 gas suppression system(2159 series)
Fire pump
Fire hose/hose reel and cabinet
Abc powder/co2 fire extinguisher
Emergency light system

 

 

Related Products

 

Certifications

 

FAQ

Q1:Can I have a sample order?

A:Yes,we welcome sample order to test and check quality.

 

Q2:What is the lead time?

A:Sample needs 1-3 days, mass product according to your quantity.

 

Q3:How do you ship the goods and how long does it take arrive?

A:We usually ship by DHL,UPS,FedEX or by Air. 3-5 days after payment received.

 

Q4:Do you guarantee for the products?

A:Yes,we offer one year guarantee for the products.

 

Q5:Do you offer OEM service?

A:Yes,we can design the products according to your request.

 

 

Send your message to this supplier
* Inquiry Title
* Content
* E-mail
* Security Question

Customer Reviews total 0 items

For product pricing, customiztion, or other inquiries

Contact Supplier

Links