The automatic recovery over voltage and under voltage protective device complies with modular design standards. the circuit boards of products adopt good quality electronic components with reliable performance. when the power situation is unstable. It"s protection function will be automatically activated. once the voltage exceeds the limited range of products, it will automatically cut off so as to protect the safely of electrical equipment and persons. The device will re-supply in 1 minute, when the power returns to normal.
The green indicator display, when the power is normal supply.
The red indicator display, when the power over voltage or under voltage.
Installing: 35mm Din rail.
Parameters
Main Technical Speacification OF 40A
Rated
AC voltage 230V±10% and frequency 50Hz/60Hz
Passing Max Current
40A
Max. Loading power
8.8KVA
Over-voltage action cut-off value
>275VAC+/-5V
Normal-voltage value
165-275VAC
Under-voltage action cut-off value
<160VAC+/-5V
Over voltage and under voltage cut-off
< 1s
Electricity transmitting delay after cut-off
<60s
Self power consumption
<2W
Electric machinery life
=100000 times
Dimension
35L*70W*77Hmm
Installing
35mm Din rail
Main Technical Speacification OF 60A
Rated
AC voltage 230V±10% and frequency 50Hz/60Hz
Passing Max Current
63A
Max. Loading power
13.8KVA
Over-voltage action cut-off value
>275VAC+/-5V
Normal-voltage value
165-275VAC
Under-voltage action cut-off value
<160VAC+/-5V
Over voltage and under voltage cut-off
< 1s
Electricity transmitting delay after cut-off
<60s
Self power consumption
<2W
Electric machinery life
=100000 times
Dimension
35W*66L*84Hmm
Installing
35mm Din rail
Noted: When you first connect the product, you have to wait about 1 minute, after the red light turn off, then the product will work.
Customer Reviews total 0 items