range of product | Harmony XB7 |
product or component type | Push-button |
device short name | XB7 |
mounting diameter | 22 mm |
sale per indivisible quantity | 10 |
shape of signaling unit head | Round |
type of operator | spring return |
operator profile | Black flush, unmarked |
contacts type and composition | 1 NO |
connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1 Screw clamp terminals, 1 x 0.34...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1 |
height | 29 mm |
width | 29 mm |
depth | 52 mm |
terminals description ISO n°1 | (13-14)NO |
net weight | 0.02 kg |
device mounting | Fixing hole - diameter: 22.5 mm 22.3 +0.4/0 conforming to EN/IEC 60947-1 |
fixing center | >= 30 x 40 mm (support panel) metal - thickness: 1…6 mm >= 30 x 40 mm (support panel) plastic - thickness: 2…6 mm |
fixing mode | Fixing nut beneath head: 2…2.4 N.m |
contact operation | Slow-break |
positive opening | With (only NO) |
mechanical durability | 1000000 cycles |
tightening torque | 0.8…1.2 N.m conforming to EN 60947-1 |
shape of screw head | Cross compatible with JIS No 1 screwdriver Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
short-circuit protection | 4 A cartridge fuse type gG conforming to EN/IEC 60947-5-1 |
[Ui] rated insulation voltage | 250 V (pollution degree 3) conforming to EN/IEC 60947-1 |
[Uimp] rated impulse withstand voltage | 4 kV EN/IEC 60947-1 |
[Ie] rated operational current | 0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1 0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1 0.3 A at 240 V, AC-14, D300 conforming to EN/IEC 60947-5-1 0.6 A at 120 V, AC-14, D300 conforming to EN/IEC 60947-5-1 |
electrical durability | 1000000 cycles, DC-13, 0.3 A at 24 V, operating rate <216000 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 0.03 A at 230 V, operating rate <216000 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 0.09 A at 240 V, operating rate <108000 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
electrical reliability | Λ <= 10exp(-6) at 17 V, 5 mA conforming to EN/IEC 60947-5-4 |
protective treatment | TH |
ambient air temperature for storage | -40…70 °C |
ambient air temperature for operation | -25…70 °C |
overvoltage category | Class II conforming to IEC 61140 |
NEMA degree of protection | NEMA 12 conforming to UL 50 E NEMA 3 conforming to UL 50 E |
standards | EN/IEC 60947-5-1 EN/IEC 60947-1 CSA C22.2 No 14 UL 508 JIS C8201-5-1 JIS C8201-1 |
product certifications | CCC GOST |
vibration resistance | 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6 |
shock resistance | 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |
Customer Reviews total 0 items