The system automatically according to the start/stop temperature, identify work mode;
Start temperature > stop temperature, cooling mode "C".
Start temperature < stop temperature, heating mode "H".
2.Cooling mode:
When the temperature ≥ Start temperature, relay conduction, red led on, refrigeration equipment begin to work;
When the temperature ≤ Stop temperature, relay disconnect, red led off, refrigeration equipment stop to work;
3.Heating mode:
When the temperature ≤ Start temperature, relay conduction, red led on, heating equipment begin to work;
When the temperature ≥ Stop temperature, relay disconnect, red led off, heating equipment stop to work;
4.Temperature correction function OFE (-10.0 ~ 10℃):
The system is working for a long time and may be biased, through this function correction, the actual temperature = measuring temperature + calibration value;
How to set the start/stop temperature:
1. In the running interface, Long Press TM+ key more than 3 seconds, into the start temperature settings interface, can be modified by TM+ TM- key, to be modified, waiting for 6s automatic exit and save;
2. In the running interface, Long Press TM- key more than 3 seconds, into the stop temperature settings interface, can be modified by TM+ TM- key, to be modified after the parameters, waiting for 6s automatic exit and save;
The humidity function is as follows:
1.The automatic identification of work mode:
The system automatically according to the start/stop humidity, identify work mode;
When the humidity≥ Start humidity, relay conduction, green led on, dehumidification equipment begin to work;
When the humidity≤ Stop humidity, relay disconnect, green led off, dehumidification equipment stop to work;
3.Humidification mode:
When the humidity≤ Start humidity, relay conduction, green led on, humidification equipment begin to work;
When the humidity≥ Stop humidity, relay disconnect, green led off, humidification equipment stop to work;
4.Humidification correction function RH (-10.0 ~ 10%):
The system is working for a long time and may be biased, through this function correction, the actual humidity = measuring humidity + calibration value;
How to set the start/stop humidity:
1. In the running interface, Long Press " RH+ " key more than 3 seconds, into the start humidity settings interface, can be modified by RH + RH - key, to be modified, waiting for 6s automatic exit and save;
2. In the running interface, Long Press " RH-" key more than 3 seconds, into the stop humidity settings interface, can be modified by RH+ RH- key, to be modified after the parameters, waiting for 6s automatic exit and save;
Customer Reviews total 0 items