Homepage|Business Center|Save the Page|Get the App
普通会员

Shenzhen Asenware Test & Control Technology Co., Ltd.

Product Category
  • No Category Yet
Search
 
Link
  • No links
Home > Products > Data processing center extinguishing system FM200
Data processing center extinguishing system FM200
Click on the image to view the original image
Product: views:5Data processing center extinguishing system FM200 
Branch: Asenware
Unit Price: Negotiated
Min.Order:
Supply:
Delivery: Shipment within days since the date of payment
Valid until: Long Term
Updated on: 2019-11-19 18:28
  Negotiated
Product Details
Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
Asenware
Model Number:
AW-GEC2159
Usage:
Fire Protection
Zone:
1/2Zones
Color:
Red
Alarm function:
High Decibel Alram Sound
Material:
Iron
Function:
Fire suppression
Warranty:
1 Years
Company type:
Manufactor
Feature:
FM200
Keyword:
Fire Alarm Control Main Panel System
Supply Ability
Supply Ability:
1000 Piece/Pieces per Month
Packaging & Delivery
Packaging Details
Carton box
Port
ZHONGSHAN
Lead Time:
Quantity(Pieces)1 - 1011 - 100101 - 1000 >1000
Est. Time(days)31530To be negotiated
Product Description

The automatic extinguisher control panel AW-GEC2169 is designed execute European standards of EN54-2 and EN54-4 Fire Detection and Fire Alarm systems clause,and Control and Indicating Equipment EN12094-1 firefighting system standards.
EN54-2 Fire detection and fire alarm systemspart 2: control and indicating equipment
EN54-4 Fire detection and fire alarm systemspart 4: power supply equipment
EN12094-1 Fixed firefighting systems - Components for gas extinguishing systems
Requirements and test methods for electrical automatic control and delay devices
AW-GEC2169 with a new design, easy to operate, metal box opening and closing door with visible glass window, make the Panel running more safe.

Product Features

The AW-GEC2169 automatic gas fire extinguisher panel has the following features:

The AW-GEC2169 automatic gas fire extinguisher panel has the following features:
Alarm input : two alarming zone signal input , 16 detectors could be connected to each zone
EM valve output : control the output of EM valve.
Panel output: line fault output / alarm output / fire extinguishing signal output/24VDC output
Power output: resettable 24VDC output, 200mA current limit protection
Automatic power switching: 220V AC power and standby battery power can be switched automatically.

The AW-GEC2169 automatic gas fire extinguisher panel has the following features:

Three levels of access control (view, operation, settings)
Fault detection with display: Real-time detect working condition of input, output, system, power, ground, fuse,and so on.
Manually disable function: Manually disable the Panel functions and zones devices.
Evacuation: Manually activate the fire alarm devices.
Silence operation: Manual silence the horns alarm and panel buzzer .
Delay time setting: You can manual set the Panel reseting time and Release delay time.
Panel Security Protection : outside cabinet with Visible glass window of opening and closing door .
tability: long-term rigorous testing before leaving the factory, the Panel is stable, safe and reliable;

Technical Parameter
AC INPUT
 220VAC 50HZ
DC OUTPUT at Power Board
24VDC (19V-28V) and 5VDC (4.9V-5.1V)
Voltage for MCU
5V for power board MCU, 3.3V for others
Current at 24VDC from PSE
<450mA standby current
Maximum current from PSE
1.4A except batteries charge
Batteries current
1.85A maximum, current limited
Auxiliary output
24VDC, 200 mA max, current limited
Extinguishant release delay time
Adjustable 0 to 60seconds(5 second steps)
Imin, Imax.a and Imax.b according to EN54-2
Imin=340mA, Imax.a=424mA, Imax.b=1.4A
Batteries
2*12V/ 2.3Ah sealed lead acid gel, self-regulated
Battery replace Resistance
1.6Ω±10% if needed
Battery low-voltage protection
21V
The maximum and minimum electrical ratings for each input and output
Detectots / zone lines: 15.2V-28V Sounder lines:19-28V
Fire protection/Fire routing lines:19-28VFault routing lines:
18-28V
Detectors wiring allowed each zone
16 points
Max points (detector and MCP) per CIE
32 points
Zone alarm current
6mA minimum/ 27mA maximum
Sounder output
200mA maximum
Fire routing/ Fault routing
200mA maximum each terminal
Communication protocol
2 wires RS485 bus system
EOL resistor for zone, inputs(Except for main power) and outputs
6.8K 1W
Wires for 220V AC IN (recommended)
16AWG
Wires connect power board to interface board (recommended)
20AWG
Wire for main board wiring with interface board (recommended)
28AWG
Fuse on power board
3A/ 250V Glass tube fuse 5*20(mm) Fast/quick blow
Fuses on interface board(general outputs)
0.2A /250V Glass tube fuse 5*20(mm) Fast/quick blow [*5pcs]
Fuse on interface board(Main Power)
2A/ 250V Ceramic tube fuse 5*20(mm) Slowly blow
Fuse on interface board(EM valve)
1.5A/ 250V Glass tube fuse 5*20(mm) Fast/quick blow
Environmental
Class A temperature range: -5 to 40°C (23~104°F)
Humidity: 
5 to 95% RH, non-condensing
Terminal blocks rating
All terminals rated for 12 to18 AWG
Wires between interface board (Panel)and Detector 
2-core shielded cable for 12 to18 AWG
Our Service

1.Professional and experienced R&D team can offer free technical support and project support.
2.Prompt reply all-around and all-weather.
3.OEM/ODM services
4.One year warranty and technical maintenance.

FAQ

Q1: Are you manufacturer?
A: (yes)
Q2: What is the lead time?
A: one week working day
Q3: How do you ship the goods and how long does it take arrive?
A: We usually ship by DHL, UPS, FedEx or by Air. 3-5 days after payment received.
Q4: Can I have a sample order?
A:Yes,we welcome sample order to test and check quality.
Q5: Do you offer OEM service?
A: Yes, we can design the things according to your request.

Certifications
Contact us

EMAIL.

sales09(@)asenware.com.

skype.

sales09_155

TEL.(Whatsapp/Wechat).

008613590128969

询价单