FAQ
8kg hfc-227ea AUTO Fire Extinguisher
Suitable for combating fires
Combustible Solids, Flammable Liquids and Gas, Live Electrical Equipment
easier clean up after fire
Technical Data :
Capacity : 8kg+-10%
Cylinder size: D295*H295mm
Stored pressure(20C): 1.0Mpa
Action temperature: 68C
Max.working pressure: 1.5Mpa
Range of Operating Temperature: 0℃~+50℃
Accessories :
Nickel plating sprinkler valve 68°
With electroplating ring M10*1 as bottom bracket
Packing Details :
by none fumigation wooden case
Operating Instruction :
Haning the fire extinguisher in the ceiling;
When the temperature reachs 68C,the sprinkler bulb bursts allowing the contents
to release under pressure and cover the fire.
Maintenance :
1.User should compute the heptafluoropropane supply quantity according to the inside volume of the protective area , around 0.64kg/m3 for computer room, 0.66kg/m3 for intertank, power switching room, power generator room and transformer room, 0.81 kg/m3 for archive room.
2.The fire extinguishing device should be installed over the area which is easy to have fire so that the heat sensitive bulb can respond quickly to extinguish a fire.
Points to note
1.The fire extinguishing device should be kept in dry place, avoid collision and protected from direct sunlight.
2.Doors and windows inside the protective area should be closed.
3.User shall have designated a person to regularly check the pressure gauge and recharge nitrogen when the pressure gauge pointer is lower than the green area, and examine the extinguishing device for leakage whenever necessary.
Min Order : 10pcs
Delivery Time : 10 ~ 20 days after prepaid
Loading and Shipment of Fire Extinguisher :
Fire extinguisher are dangerous goods under IMO 1044 class 2.2
by international sea bureau so all the shipment must shipped as DG cargo.
1. All cartons must stick IMO green label.
2. All container must pull green net
3. Danger shipping mark "1044"
Customer Reviews total 0 items